Service Issue - Network Connectivity - Washington, DC

Incident Report for Linode

Postmortem

On March 10, 2025, between 17:50 and 18:10 UTC, we experienced intermittent connectivity disruptions and origin forward errors due to a power supply unit (PSU) mishap at our fabric site in Washington DC (US-IAD), which impacted multiple customers.

The issue was caused by human error during data center maintenance, where a working PSU was mistakenly unseated instead of the faulty one. This confusion arose due to the similar appearance of two different PSU models and their distinct indicator lights. While the working PSU was re-seated at 17:52 UTC, the impact persisted until 18:10 UTC.

We take full responsibility for the error and are updating our procedures to prevent similar issues in the future.

We sincerely apologize for the disruption and appreciate your patience as we work to ensure the continued reliability of our services.

This summary provides an overview of our current understanding of the incident given the information available. Our investigation is ongoing and any information herein is subject to change.

Posted Mar 24, 2025 - 20:18 UTC

Resolved

We haven’t observed any additional connectivity issues in our Washington, DC data center, and will now consider this incident resolved. If you continue to experience problems, please open a Support ticket for assistance.
Posted Mar 11, 2025 - 01:00 UTC

Monitoring

At this time we have been able to correct the issues affecting connectivity in our Washington, DC data center. We will be monitoring this to ensure that it remains stable. If you are still experiencing issues, please open a Support ticket for assistance.
Posted Mar 10, 2025 - 21:13 UTC

Investigating

Our team is investigating an emerging service issue affecting network connectivity in our Washington, DC data center. We will share additional updates as we have more information.
Posted Mar 10, 2025 - 18:37 UTC
This incident affected: Regions (US-IAD (Washington)).